Operating Characteristic of 0.6/1KV Copper XLPE Power Cable
Rated voltage: 0.6/1(1.2)kV;
Max. permissible continuous operating temperature of conductor: 90 °C;
Max. temperature of conductor during short-circuit (5s max. duration) shall not exceed: 250 °C;
The ambient temperature under installation should not be lower than: 0 °C.
The bending radius of cable is recommended as following:
For single core cable: not less than 15 times of the diameter of cable
For multi-core cable: not less than 12 times of the diameter of cable
When the armoured single core cable used for Alternative Current(AC) system, the armour material should be non-magnetic.
Application of 0.6/1KV Copper XLPE Power Cable
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid in high fall area, able to bear external mechanical force, and certain pulling force.
Manufacturing Standard of 0.6/1KV Copper XLPE Power Cable
GB/T 12706-2008, IEC 60502-1