Aerial Insulated Cables with Rated Voltage 10 kV
10 kV Aerial Insulated Cables Standards Implemented
This product is produced according to the national standard GB/T14049-2008, applicable to the AC rated voltage U (Um) of 10 (12) kV for overhead power line steel core, aluminum core cross-linked polyethylene or high-density polyethylene insulated aerial cable.
Type and Designation
Type |
Product Designation
|
Main application |
JKYJ |
Cu core XLPE aerial insulated cable |
Overhead fixed laying, soft copper core products for the transformer lead, cable erection, should be considered to maintain a certain distance with the trees, the cable is running, allowing the cables contact with trees frequently. |
JKTRYJ |
Soft Cu core XLPE aerial insulated cable |
JKLYJ |
Al core XLPE aerial insulated cable |
JKY |
Cu core PE aerial insulated cable |
JKTRY |
Soft Cu core PE aerial insulated cable |
JKLY |
Al core PE aerial insulated cable |
JKLYJ/B |
Al core with essential color XLPE aerial insulated cable |
as above |
JKLYJ/Q |
Al core light XLPE aerial insulated cable |
When the cable is erected, it should be considered to maintain a certain distance from the trees. When the cable runs, only short-term contact between the cable and the tree is allowed. |
JKLY/Q |
Al core light PE aerial thin insulated cable |
The Specification of Aerial Insulated Cables with Rated Voltage 10 kV
Type |
Number of core |
Rated voltage
10(kV) |
Nominal section (mm2) |
JKYJ,JKTRYJ,JKLYJ |
1 |
10-300 |
3 |
25-300 |
3+K(A)
OR3+K(B) |
25-300 |
In which. K is 25-120 |
JKY,JKTRY,JKLY,
JKLYJ/Q,JKLY/Q |
1 |
10-300 |
JKLYJ/B |
3 |
25-300 |
3+K(A)
OR3+K(B) |
25-300 |
In which. K is 25-120 |
Remarks:
(1)In which,K is a supporting twisted wire,according to the requirement of the project,the specified section listed in table 2 may be selected to match with related conductor’s section.
(2) In which,(A) is a steel supporting twisted wire,and B is a Al alloy supporting twisted wire.
10 kV Aerial Insulated Cables Using Feature
Maximum long-term allowable operating temperature of the cable conductor (with load bearing structure cable)
1. Cross-linked polyethylene insulation 90℃;
2. High-density polyethylene insulation 75℃. In case of a short circuit (maximum duration not exceeding 5 seconds) the maximum temperature of the cable should not exceed:
(1). Cross-linked polyethylene insulation 250℃;
(2). High-density polyethylene insulation 150℃. The laying temperature of the cable shall not be lower than -20℃; the allowable bending radius of the cable shall not be less than the diameter of the cylinder used in the cable bending test.